On line monitoring device for insulator pollution of transmission line

model:DX-WPS100-WH

1、 Demand analysis

During the operation of the transmission line in the outdoor environment, its insulators are vulnerable to the impact of atmospheric environment such as S02, nitrogen oxides and particulate dust, thus accumulating pollutants on its surface. Under certain humidity conditions (such as fog, dewing or drizzle), when pollutants are dissolved in water to form an electrolyte covering film, or when conductive chemical gases surround the insulator, the insulation performance of the insulator will be greatly reduced, resulting in greatly increased leakage current on the insulator surface, power interruption caused by insulator flashover, and a great impact on the safe and stable operation of the power grid, Anti pollution flashover is an urgent task to maintain the normal operation of power grid. The transmission line insulator pollution online monitoring device developed by our company can completely solve this problem. The equipment can detect the pollution condition of the external insulation surface of the insulator and accurately predict the pollution flashover problem.


2、 Working principle

The online monitoring device for insulator pollution of transmission line is mainly composed of data monitoring terminal and data monitoring center. The data monitoring terminal is installed near the transmission line pole (tower) or substation insulator to complete the real-time monitoring of on-site pollutants (salt dense, ash dense), temperature and humidity. The monitoring data is sent to the monitoring center by SMS through GSM wireless network. The data monitoring center completes the conversion and processing of monitoring data.

In case of abnormal data, the system will send out alarm information in various ways to prompt relevant personnel to take corresponding measures.


3、 Product features

1. Optical sensor: it can measure salt density and ash density with high accuracy and is not affected by human factors;

2. Information receiving and sending module: receives the monitoring information sent back by the controlled monitoring terminal, and can store the salt density data for three months to ensure that no monitoring information will be lost when the host has problems;

3. Monitoring center system software: provide a full set of online pollution analysis software;

4. Host: The host is a computer server with powerful data calculation function. It can store, calculate and analyze data;

5. With the change of light energy parameters at different wavelengths, the salt density and ash density of pollutants can be calculated


4、 Technical parameters

Monitoring range of salt density: 0 ~ 0.8mg/cm2

Ash density monitoring range: 0 ~ 2mg/cm2

Working environment temperature range: - 30~60 ℃

Battery: DC 12V 12Ah

Solar cell: DC 12V 5W

Monitoring parameters: time temperature relative humidity salt density

Power consumption of the whole machine: 0.1W in monitoring state; Communication status 1W



Contact us

Shenzhen Dinsee Smart Technology Co.,Ltd
Tel:0755-21612345 Mobile&Whatsapp:+8618926454155
Fax:0755-21612345Whatsapp:+8618926454155E-Mail:business@szdx.com
Address: Building 2,xiangyuer Industry Part,NO.8 Longsheng Road,Longgang District,Shenzhen 518126,China

The online monitoring, distributed fault location and cable online monitoring equipment for power transmission and distribution lines launched by SHENZHEN DINSEE SMART TECHNOLOGY CO.,LTD. has been widely used in Southern Power Grid and State Grid, and has achieved good results.

Record No.: Yue ICP Bei 2022070794-1 | Website Map XML Map

Baidu
map